Application
Light to medium condensate loads: steam tracing, steam main drips, small heat exchangers, unit heaters, steam heating coils and many other applications in the petrochemical, chemical, textile, food, pharmaceutical and other industries.
TB7N | Steam main lines and tracing lines, low and medium pressure applications |
TB9N | Steam main lines, tracing lines, low and medium pressure applications |
TB51, TB52 | Steam tracing lines, low pressure applications |
TB81, TB82 | High pressure steam main lines, high pressure applications |
Features
Excellent air venting characteristics at start-up and during operation |
Insensitive to waterhammer |
The operation will not be influenced by back pressure |
At time of non-operation self-draining |
No steam loss throughout its operating range |
All traps equipped with integral strainers |
Can be installed both horizontally and vertically |
Easy in-line inspection and maintenance |
Lightweight, compact design |
Operation
1) Upon start-up in the presence of cold condensate, the capsule element is contracted and the valve plate has moved away from the seat. The wide open valve discharges condensate and air rapidly. |
2) As the temperature inside the trap increases, the capsule element will start to expand, moving the valve plate toward the seat. |
3) Just before the condensate reaches saturation temperature, the valve plate will close the seat completely. Steam can not enter the trap, ensuring zero steam loss. |
4) As the temperature inside the trap decreases, the capsule element moves away from the seat and the condensate will be discharged. During normal operation steps 3 and 4 will repeat continuously. |